誤差電壓 的英文怎麼說

中文拼音 [chādiàn]
誤差電壓 英文
error voltage
  • : Ⅰ名詞(錯誤) mistake; error Ⅱ動詞1 (弄錯) mistake; misunderstand 2 (耽誤) miss 3 (使受損害...
  • : 差Ⅰ名詞1 (不相同; 不相合) difference; dissimilarity 2 (差錯) mistake 3 [數學] (差數) differ...
  • : Ⅰ名詞1 (有電荷存在和電荷變化的現象) electricity 2 (電報) telegram; cable Ⅱ動詞1 (觸電) give...
  • : 壓構詞成分。
  • 誤差 : error
  • 電壓 : voltage; electric tension; electric voltage
  1. In digital relay, the percentage of noise will increase rapidly with the increase of sampling rate when derivation calculus is substituted by sampled difference term. to solve this problem, a new method using fragment function integrated with the least square algorithm is proposed in this paper. the influence of white noise is greatly reduced and the accuracy of the dead angle calculation is nicely improved after adopting the new method

    在數字式保護中,如果用分代替求導將導致噪聲的百分比隨著采樣頻率的提高而劇增,本文對此進行了分析並提出了用分段樣條函數最小二乘法來計算流波形的導數值,以便在提高采樣率的同時降低噪聲的影響,並將其應用於基於32位浮點dsp的新型變器保護裝置。
  2. Discriminator output error voltage

    鑒相器輸出誤差電壓
  3. The feedbacks of position, velocity, acceleration and dynamic pressure were applied to adjust the model, so the control system of single jar electrodraulic servo mechanism was built. to reduce the system error and interference error, the compound control was designed. the results of simulations showed that the magnitude attenuation and phase lag of the system come to the project demand

    引入包括位置反饋、速度反饋、加速度反饋和動反饋在內的反饋控制技術對液伺服驅動機構模型進行綜合校正,從而建立單缸液伺服控制系統,並在分析系統和擾動后,加入復合控制減小系統和抑制干擾,模擬結果表明復合控制系統的控製品質有了明顯改善,能夠滿足工程需求。
  4. The error pickoff is an angle-to-voltage transducer.

    檢測器是把角度轉換為的傳感器。
  5. The improved voltage model of rotor flux is proposed in the paper. it eliminates the influence to actual system function in the voltage model of rotor flux for the proper drift problem and cumulative error of pure integral calculus tache

    提出了改進的型轉子磁鏈估算模型,消除了型轉子磁鏈估算模型中純積分環節所固有的漂移問題和積累對實際系統性能的影響。
  6. On the other side, measuring errors of grounding resistance and solution of current voltage electrodes reversing has been compared with horizontal two layers and vertical delaminating ( three layers soil )

    比較分析了極反向布置、在水平雙層和垂直分層或三層土壤結構中接地阻測量的和解決辦法。
  7. The paper proceeds from the transient equation for voltage and torque, analyze the electromechanic time constant of permanent - magnet dc servomotors based on the theory, and compare with the several testing methods which are used normal in the engineering, point out the difference and applying area also for the testing error which is led to possibly

    摘要為了準確評價伺服動機的動態性能指標,從機的、轉矩平衡方程式出發,在理論上對永磁直流伺服動機的時間常數進行了分析探討,並對工程實際中常用的幾種測試方法進行分析和比較,指出其別和適用范圍以及可能造成的測試
  8. Aiming at the study actuality of fan performance monitoring system and analysis of fan performance curve changes affected by inlet - box and the different fixed - angles of guide blades in the course of installation, a fan flow monitoring model based on rbfnn in whole flow zone was established in this thesis. in the model, the method of no throttle and fan performance curve were used as basis. and on the basis of that model, fan performance curves of 4 - 73no. 8d were approached with experimental data of different speed, different opening - angles of guide blade and different resistance of pipeline, the precision and the error law of model were studied

    本文針對站風機性能監測系統研究較少的現狀,在實驗的基礎上分析了現場加裝進氣箱和由於安裝造成的導流器葉片開度不一致對風機性能曲線的影響,並在此基礎上採用無節流方法測量流量,以風機調節性能曲線為依據,建立了基於徑向基函數( rbf )神經網路的風機流量全程監測模型;以實驗室4 - 73no . 8d離心風機為研究對象,探討了rbf神經網路模型在變轉速、變導流器開度和變管網阻力等工況下的應用精度和分佈規律;最後用visualc + +語言開發了風機性能在線監測系統。
  9. It creates the model of layer soil by using the cdegs software, analyses the resistance error which is measured by traditional three - poles way, measures the grounding grids resistance and soil resistance rate of hejin power plant, creates the electromagnetic model of layer soil and grounding grids model of hejin power plant, calculates the step voltage > touch voltage n voltage distribution of earth surface in fault of hejin power plant. in the end, it compares the measuring value and calculating value of grounding grids resistance in hejin power plant

    本文利用cdegs軟體建立分層土壤接地模型,對傳統三極法測量接地進行分析;對河津廠接地網接地阻和土壤阻率進行測量;建立河津廠分層土壤磁模型和接地網模型;計算河津廠接地網阻和事故狀態下跨步、接觸和地表位分佈;最後對河津廠接地網阻實測值與計算值進行比較分析。
  10. To avoid the serious electromagnetic interferer, the analog signals are transformed to frequency pulses which are transferred to the kernel of the system. in the measure of the groove voltage, the method of float - ground is adopted to avoid the high common signal and the range switch circuit is designed to solve the conflict of the wide dynamic range and the high precision. least square curvefit is adopted to reduce the system error

    解生產現場磁干擾非常嚴重,為此我們將需要測量的模擬信號就近轉換為頻率脈沖后再傳送到控制核心;採用浮地接入方式消除槽信號中的共模成分;設計了量程自動切換路以解決槽的動態范圍寬和測量精度高的矛盾;用最小二乘法進行曲線擬和以降低測量的系統
  11. In order to make the sensitivity of 2 - demension accelerometer along the two main arbors almost identical, symmetric four - beam structure that embeds a double - sides interdigitated differential capacitive with puckered beam in two directions was used as sensitive component. in addition, the differential capacitive accelerometer fabricated by bulky silicon micromechanical technique has high sensitivity, wide measurement scope, less nonlinear error, and simple converting circuit. then, the structure parameters of the sensitive component were calculated and stimulated, which results in a set of the optimized structure design parameters, main fabrication procedure and several key fabrication technology

    為使二維振動傳感器在兩主軸方向的靈敏度大致相同,敏感元件採用高度對稱的四梁結構,其中每個軸向上均採用帶折疊梁的雙側叉指容結構,採用體硅微機械工藝製作的高深寬比叉指容式敏感元件,具有高靈敏度、寬量程、非線性小、外圍路簡單等優點;對設計的敏感元件結構參數進行了計算,並利用有限元法進行了模擬分析,根據模擬結果得出了優化參數;在確定敏感結構的基礎上,研究了敏感元件採用體硅微機械加工工藝製作的工藝流程和關鍵工藝技術;對敏感晶元內部的c - v介面路進行了原理設計與分析,利用動測量技術得到由振動引起的微小容變化量,經c - v介面路進行相位調制處理,然後通過解調輸出與加速度成正比的信號。
  12. Comparing and analyzing the synchronous control strategy, which brings up the new method to control the double un - symmetry jars proceed synchronously with the combination of proportional valve and servo valve, which forms closed loop control ; basing on the above methods, models are made to get mathematics models of position control system and to analyze system model theoretically by using pid controller, we can realize regulating parameters, minimizing synchronous errors and enhancing the dynamic performances ; the simulink tool box in matlab software is used to imitate the system according to the model, which not only makes the result visual and easy to adjust the parameters in interactive way but also lets us understand the effects of different parameters and optimizes the dynamic properties. the theory of plc control in dshp is discussed after advanced understanding of the system movements. hardware design and general regulation are given on the base of siemens company products s7 - 200 plc

    本文根據大量的國內外文獻,對研配液機的工作原理及設計結構進行了簡介;對位置同步的控制方法進行了比較分析,提出比例閥和伺服閥復合控制的閉環結構來對非對稱雙缸進行同步控制液比例同步控制方案;在此基礎上著重對比例閥控非對稱缸建模,最後得到位置控制系統的總體數學模型,從理論上對同步系統動態特性進行了分析,並用pid控制器進行參數整定,減小雙缸同步、提高系統的動態響應性能;其中控制性能的分析藉助于matlab軟體中的simulink工具箱,由已建立的數學模型形成模擬模型,得到可視化的模擬結果,從而利於交互方式下調整參數,了解不同的參數對系統的影響,優化同步系統的動態性能;在深入了解系統的動作特性后,對plc控制研配液機的原理進行了探討,針對siemens公司s7 ? 200型plc給出了硬體設計的總體規劃,編制出研配液機動作控製程序,在編程中著重研究位移傳感器與plc的通訊、雙缸同步運行的pid控制在plc上的實現及bcd碼撥盤輸入程序的植入問題。
  13. For the existing transformer cooling control system has many shortcomings such as the complicated system control circuit, the low reliability, the protection methods of blower fan being so simple, large control error, high fault rate, massive maintenance work and no method to realize telecommunication, this thesis develops a novel intelligent power transformer air - cooled control system based on the center of microprocessor through all - round technology analysis and research

    本文針對變器冷卻系統使用常規控制系統存在的系統控制迴路復雜、可靠性低、風機的保護方式簡單而無法進行故障預測、主變器油溫測量精度低造成控制大、故障率高、維護工作量大、無法實現遠程通訊等問題,經過多方面的技術分析和調研,設計開發了新型的以微處理器為核心的智能式力變器風冷卻器控制系統。
  14. Output errors of power amplifiers, hysteresis and creep error of pzts and coupling error among the actuators are the critical factors affecting the motion accuracy of improvement

    摘要功率放大器的輸出陶瓷的洄滯及蠕變、驅動器之間的耦合等是影響機器人運動精度的關鍵因素。
  15. They are also capable of handling high peak voltages and currents

    能處理高峰值流,容量
  16. During the traditional measurements of the reactive power, the asymmetry of the voltage and current arises the asymmetry error

    傳統的三相無功功率測量中的由流不對稱引起的「不對稱」 ,長期以來一直是個難以解決的問題。
  17. Analyze item by item the position of unintact cycle, the running clearance of unintact cycle, locking - deform, datum dimension regulating, repeatly install, power voltage wave and marking running etc. at the same time, we give the calculating formula to calculating the running marking random error, and use it to calculate the system error of big diameter measure instrument - - datum dimension frame error, gyro - wheel diameter error, error caused by circumstance temperature, error caused by backing distance, angle error, delay error of data collecting circuit, lathe main shaft running error, workpiece install partial error

    對不完整圓的位置、不完整圓的轉動間隙、鎖緊變形、基準尺調整、重復安裝、波動、標記轉動等隨機進行了逐項分析,並給出轉動標記隨機的計算公式。對大直徑測量儀的系統?基準尺尺架、滾輪直徑、環境溫度引起的、後退距離引起的、角度、數據採集路延時、車床主軸回轉、工件安裝偏心分別進行了計算,最後對進行合成。
  18. Based on the output - voltage error function, a novel time discrete modulation technique is proposed for matrix converters ( mcs ) and time - discrete difference equations of a mc circuit are derived

    摘要針對矩陣變換器調制方式的特點,提出了基於輸出函數分析的矩陣變換器離散調制技術,推導了基於時間離散和分原理的路方程。
  19. The synchronous rectifying and low power sampling technology is used to reduce the power consumption, flexible external loop compensation, error amplifier output clamp are adopted for better system large signal response. the piecewise slope compensation technology is employed to minimize the consequence of over compensation. the sensor resistor is externally connected, which realize output voltage programmable. the overheat protection and under voltage protection modules are integrated in the die to allow the reliable operation of the system

    同時,路設計採用同步整流技術、低功耗流采樣技術降低功耗,提高轉換效率;採用靈活的外部環路補償技術、放大器輸出嵌位技術以實現良好大信號特性;採用分段斜坡補償技術,消除不穩定因素,並最大程度地減小過補償帶來的問題;採用外接輸出采樣阻的方式,實現輸出的可編程。
  20. The frequency of the pulse is the same as that of the crystal oscillator. the pulses sampled the output of the vco and generate the error signal. the error signal is amplified,

    誤差電壓經放大後送入環路濾波器進行濾波和再放大,然後去改變變容管偏置,控制振蕩器輸出頻率,達到穩頻的目的。
分享友人