  1. Finally this paper propose the structure diagram of adaptive distance protection based on neural network impedance relay, which describes entire logic procedure from data acquisition unit to trip unit

    最後提出基於神經網路繼電器的自適應結構框圖,描述從信號採集單元到動作出口單元的整個邏輯過程,並對自適應的前景作出展望。
  2. This paper discusses the ability of avoiding maximal power flow of quadrilateral impedance relay and round impedance relay in detail and puts forward the setting principle and setting method of load limiting resistor of backup distance protection

    本文對四邊形和方向圓特性繼電器躲線路最大潮流的能力進行了詳細分析,提出了負荷限制電的整定原則和整定方法。
  3. Applying relative arithmetic to all kinds of faults and calculating off - line, we can master time - distance relation chart for all kinds of faults. computation indicates : when transmission lines occur faults, the data window of protection algorithm consisting of prefault and postfault data at the same time has important significance. the following methods are useful to achieve the inverse time characteristic : calculating impedance by using flourier in a full cycle, calculating work voltage by using fault component, calculating the torque created by a phase comparator or a magnitude comparator

    實際的計算表明:輸電線路發生故障后,用故障前後的數據同時充滿演算法的數據窗,對于快速切除近區故障具有很重要的意義;同時利用故障前後的數據,下述方法可以比較好地實現的反時限特性:直接用全周傅里葉演算法進行計算;採用工頻變化量繼電器進行工作電壓的計算;採用轉矩的思想進行轉矩的計算。
  4. But due to the existence of the fault resistance, the branch current, the zero sequence mutual coupling and so on, the apparent impedances and protection scope of distance protection will change, thereby affecting the performance of distance protection and the safety operation of power system

    然而,由於過渡電、分支電流和零序互感等因素的影響,會改變測量的大小,造成動作范圍的擴大與縮小,從而影響的性能,威脅電力系統的安全運行。
  5. A tentative idea of using the variation of interim resistance to achieve the metering ofadapting oneself to impedance is put forward, the relevant bases of a differentiation are derived, and its preliminary analysis has been carried out as well. it aims at eliminating the influence of interim resistance on metering of impedance protector by changeable property of arc resistance

    提出了利用過渡電增量實現自適應測量的設想,導出了其動作判據,並對該判據進行了初步分析,旨在利用故障點電弧電的變化特性來消除過渡電正確測量的影響。