tangqian 中文意思是什麼

tangqian 解釋
塘前
  1. Tangyin substation is an important substation which has two transformer of 120mva, eight 220kv lines and three 110kv lines. tangqian line is a 110kv line specially for traction transformer substation. because traction load is high - power nonlinear and asymmetry. it will produce much harmonic and negatvie sequence current, which have done harm to compensation capacitors of tangyin substation. in recent years, the tang6c capacitor often interrupted and in 2001 july the tang7c capacitor ' s discharge pt exploded

    湯陰變電站是豫北一座樞紐變電站,有2臺120mva的主變, 8條220kv線路和3條110kv線路,其中的湯牽線是專為牽引變電站供電的110kv線路。由於電力機車屬于大功率的非線性負荷,且三相不對稱,在其運行過程中必然會產生較大的高次諧波和負序電流。
  2. In accord with the state standard about harmonic. the harmonic permission value of tangqian line is calculated. some measurement data are shown and analyzed, and some main conclusion is drawed that the 7th harmonic voltages of tangqian line is near to the permission value, total harmonic voltage distortion ratio has oversteped the permission value. the 3th harmonic, the 5th harmonic, the 7th harmonic and the 9th harmonic current from tangqian line all overstep the permission, the largest 5th harmonic current ratio in tangsc reaches 44 %, the 7th harmonic and the 9th harmonic current in tang7c and tangsc is large maybe because the harmonic current is magnified. this paper studies the model of each element in tang yin substation

    根據有關公用電網諧波的國家標準,計算出湯牽線注入湯陰變電站的諧波電流允許值,從實測數據可以得出一些重要結論:湯牽線7次諧波電壓含有率的最大值接近國標中的限值,湯牽線的諧波電壓總畸變率的最大值已超標;湯牽線注入電網的3 、 5 、 7 、 9次諧波電流都超標;湯6c電容器的5次諧波電流含有率較高,最高達到44 ;湯7c和湯8c電容摘要器的7次和9次諧波電流含有率偏高,原因可能是發生了諧波電流放大現象。
分享友人