  2. During unit startup and load is lower than 15 %, drum level is controlled by feedwater control valve, feedwater pump remains at minimum safety speed ; when load is between 15 % and 25 %, feedwater control valve is closing at fixed speed determined by function module, main motor - operated - valve is opened automatically, control mode of drum level is transferred to feedwater pump automatically and bumplessly ; when load is between 25 % and 50 %, control valve is closed fully, and main motor - operated - valve is open fully, drum level is controlled by one pump ; when load is more than 50 %, first pump is kept in operation, second pump is putting into operation automatically and

    在機組、沖轉及機組並網至15 %負荷階段,給維持在最低安全轉速下運行,汽包位由低負荷給調節閥控制; 15 %至25 %負荷階段,給調節閥由函數模塊按照一定的速率平滑關閉,主給打開,汽包位控制方式無擾切換為給控制;負荷在25 %至50 %階段時,給調節閥已完全關閉,主給門已完全打開,位控制已全由單臺給承擔;負荷大於50 %后,在第一臺給運行的同時,第二臺給無擾投入。