諧波電流 的英文怎麼說

中文拼音 [xiédiànliú]
諧波電流 英文
harmonic current
  • : Ⅰ形容詞1 (和諧) in harmony; in accord; in tune 2 (詼諧) humorous Ⅱ動詞(商量好; 辦妥) come t...
  • : Ⅰ名詞1 (波浪) wave 2 [物理學] (振動傳播的過程) wave 3 (意外變化) an unexpected turn of even...
  • : Ⅰ名詞1 (有電荷存在和電荷變化的現象) electricity 2 (電報) telegram; cable Ⅱ動詞1 (觸電) give...
  • : Ⅰ動1 (液體移動; 流動) flow 2 (移動不定) drift; move; wander 3 (流傳; 傳播) spread 4 (向壞...
  • 電流 : current; galvanic current; electric current; electricity; current flow電流保護裝置 current protec...
  1. An adaptive harmonic current calculation arithmetic for apf using pll - produced reference voltage

    產生參考壓的自適應諧波電流檢測方法
  2. The way of taking one nth out of capacitor ' s the first harmonic capacitive reactance as its nth harmonic impedance is verified whit the data from tang7c. according to the approximately estimating method, the first harmonic impedance of 220kv system is calculated. on the basis of the models, this paper gives the harmonic equivalent circuit of substation and gives the b ( n ) function of the harmonic time n. when the capacitors has different combination, b ( n ) ' s value will also change, with the inputting local measurement data, the paper studies the series and parallel resonance at the substation, and deduces that the reason the capacitor ' s fuse of tang6c is frequently interrupted is that its capacitor current contains a large number of 5th harmonics, and that the reason the discharging pt of tang7c capacitor being exploded is also that the 7th and 9th harmonic currents are amplified

    據此,對該站進行了串聯振分析和並聯振分析,並結合測試數據和有關變站的運行記錄,指出了導致該站容器湯6c頻繁燒保險的主要原因是5次諧波電流含量偏高,引起湯7c放pt爆炸也是因為7次和9次諧波電流被放大。針對這些導致湯陰變站補償容器故障的原因,提出了相應的治理措施,包括針對湯6c容器5次諧波電流含量偏高的原因,提出了停運湯6c容器或者通過把湯sc容器的部分容量併入湯6c容器(湯sc其餘部分停運)以增加湯6c承受能力的措施;針對# 2變低壓側7次和9次諧波電流被放大的現象,提出了在湯7c容器上加裝一定百分比的串聯抗器的措施。
  3. Series reactor is applied to ac power system with rated voltage of 6kv - 63kv and series connected with shunt capacitor banks for restraining wave distortion in grid voltage so as to improving the quality of power system and ensure the safety of its operation. it can restrain harmonic current and surge current in capacitor banks so that the capacitor will operate reliably

    Ckdk型串聯抗器,適用於6 63 kv力系統中,與並聯容器相串聯,用以抑制形畸變,從而改變網質量和保證力系統安全運行抑制容器組的諧波電流和限制合閘涌,從而保護容器的安全可靠運行。
  4. Dry - type air - cored series reactor is applied to ac power sys - tem with rated voltage of 6kv 10kv 35kv and series connected with shunt capacitor banks for restraining wave distortion in grid voltage so as to improving the quality of power system and ensure the safety of its operation

    乾式空芯串聯抗器適用於6kv 10kv 35kv力系統中與並聯容器組串聯,用於抑制形畸變,從而改善網質量和保證力系統安全運行,抑制容器組的諧波電流和限制合閘涌,從而保護容器使之安全運行。
  5. With adaptive ability, harmonic current detecting approach, based on ann, can accurately and real - timely detect harmonic currents for power network

    基於人工神經元自適應的諧波電流檢測方法,能夠準確、實時地檢測網中的,且有一定的自適應能力。
  6. Therefore it is the sticking point for solving the problem about separating the duty to find methods by which the customer emission level can be accessed ( the voltage that a customer ' s harmonic current begets at the point of common coupling ) more accurately

    由於劃分的依據主要由用戶與力系統雙方發射的諧波電流在公共聯接點引起的壓降的比例決定,因此,尋求對用戶發射水平(用戶諧波電流在公共聯接點所引起的壓降)的準確估計方法,成為了解決責任劃分問題的關鍵。
  7. Finally, the method of estimating power customer emission level based on binary linear regression is put forward, which make it a condition that harmonic emission is steady at the point of common coupling. combined with power system thevenin equivalent and customer norton equivalent, according to the principle of least squares method, the voltage that a customer ' s harmonic current begets at the point of common coupling can be estimated in the light of the plural correlation of network parameters

    最後,提出了基於二元線性回歸的用戶發射水平估計方法,該方法在假設公共聯接點發射穩定的情況下,結合系統側戴維南等值與用戶側諾頓等值的路圖,按照最小二乘法原理,利用網各參數的復數關系推導關于系統側阻抗的二元線性回歸方程,並根據阻抗的估計值求取用戶諧波電流在公共聯四川大學碩士學位論文( 2003 )接點產生的壓降。
  8. The basic idea is that increasing the equivalent harmonic impedance of power network by valid control of active filter, in order to enhance the performance of passive filter and damp the resonance between the passive filter and the equivalent inductance of the power network

    無源支路在補償無功功率的同時還可以濾除因非線性負載產生的特徵諧波電流,為了抑制無源支路跟網等效感產生的振現象以及改善無源濾器的濾性能,系統中採用振注入式有源濾拓撲。
  9. Most of the traditional real - time detecting method for harmonic current is based on sinusoidal voltage or locking the voltage phase accurately, which deviating from the real circumstances

    由於傳統的諧波電流實時檢測方法大都是基於正弦的壓系統或對于形達到精確鎖相的前提,而現實情況卻往往不是如此。
  10. Many experts and researchers have made great efforts in a long time. this paper is from the study of theory, analysis the particularity of electrical tractor loads

    本文從理論探討的角度出發,深入了解了國內外對牽引系統多源隨機諧波電流疊加問題的動態,分析了牽引負荷的分佈特性。
  11. One approach to minimize this impact is to filter the harmonic currents and the electromagnetic interference ( emi ) produced by the power electronic loads

    減小這種影響的一個辦法是,將由子負載產生的諧波電流或者磁干擾濾除。
  12. When zero sequence or high secondary harmonic current component appear in the circuit, the total current in the shield is zero, no electromagnetic interference with outside

    當線路出現零序或高次諧波電流分量時,屏蔽層內總和為零,不對外界產生磁干擾。
  13. It is found that the electron beam may approach ideal bunching. high power microwave pulses with tunable frequency can be generated by post - accelerating the electron beam and carefully designing the extraction cavity. in terms of the pic simulation, the output power of 1. 25gw at 2. 2ghz and 480mw at 4. 4ghz in axial acceletron have been obtained

    用增加中間腔的辦法,大大提高了前兩階諧波電流分量,數值計算結果表明,其中一階諧波電流調制系數達到了140 ,二階諧波電流調制系數達到了68 ,通過改變提取腔的設計,可選擇不同頻率的輸出,其一次頻率為2 . 2ghz ,輸出功率為1 . 25gw ,效率為9 . 33 ,二次頻率為4 . 4ghz時,輸出功率為0 . 48gw ,效率為3 . 6 。
  14. For a class of shunt - wound active power line conditioner, based on analysis of mathematical model of system and target of control, the algorithm of fuzzy variable structure sliding mode control is presented. the control algorithm can avoid complicated calculation of harmonic electric current in traditional control algorithm, and realize the feedback control of electric current. the algorithm is simple and easily implemented

    針對一類並聯型有源網調節器在分析系統數學模型和控制目標的基礎浙江大學博士學位論文上,提出了模糊滑模控制策略,避免了傳統控制方法中復雜的諧波電流計算,實現對的閉環控制,該演算法簡單、易於實現,模擬結果證實了變結構滑模控制的有效性。
  15. In accord with the state standard about harmonic. the harmonic permission value of tangqian line is calculated. some measurement data are shown and analyzed, and some main conclusion is drawed that the 7th harmonic voltages of tangqian line is near to the permission value, total harmonic voltage distortion ratio has oversteped the permission value. the 3th harmonic, the 5th harmonic, the 7th harmonic and the 9th harmonic current from tangqian line all overstep the permission, the largest 5th harmonic current ratio in tangsc reaches 44 %, the 7th harmonic and the 9th harmonic current in tang7c and tangsc is large maybe because the harmonic current is magnified. this paper studies the model of each element in tang yin substation

    根據有關公用的國家標準,計算出湯牽線注入湯陰變站的諧波電流允許值,從實測數據可以得出一些重要結論:湯牽線7次壓含有率的最大值接近國標中的限值,湯牽線的壓總畸變率的最大值已超標;湯牽線注入網的3 、 5 、 7 、 9次諧波電流都超標;湯6c容器的5次諧波電流含有率較高,最高達到44 ;湯7c和湯8c容摘要器的7次和9次諧波電流含有率偏高,原因可能是發生了諧波電流放大現象。
  16. The widely applications of nonlinear instruments have produced many high order harmonics, they are flowing into the power network and greatly influence the quality of electric power. and the frequency is n ' t constant but changed around 50hz

    網中非線性設備的使用日益增多,所產生的高次諧波電流大量注入力線路中,使得壓、形發生畸變,同時網頻率並不是固定不變的,而是在50hz附近動。
  17. The electric power harmonic comprehensive control system with low cast and high security is applied in this article. it adopts that sourced compensation links with non - sourced compensation herewhich the former is realized by high frequency pwm control technology and the latter is carried out by crystal switch formed by non - flow and over - voltage. it can realize stepless modulation with imaginary power, mightiness compensation of harmonic and negative electricity, and circuitry consumption debasing are achieved

    提出採用有源補償與無源補償相結合的綜合治理技術及裝置,無源部分採用無涌和過壓的晶閘管控制容器技術實現,有源部分採用高頻pwm控制技術實現,成本低、可靠性高、可實現無功功率的無級調節、強力補償諧波電流和負序,降低線路損耗。
  18. Areas covered in the review include bonding requirements, lightning protection requirements and harmonic current limits requirements. we are updating the reference list for international standards and adding an index page for quick reference

    今次修訂的內容包括等位接駁的要求、避雷系統的測試方法及諧波電流的限制,並更新國際標準的參考資料及新加索引等。
  19. Test items : insertion loss ; disturbance voltages ; radiated electromagnetic disturbances ; harmonic current ( emission )

    磁兼容檢驗項目:插入損耗;騷擾壓;輻射磁騷擾;諧波電流
  20. Because the harmonics in tangyin substation are primarily from electric traction loads, this paper gives the structures of several main locomotive models and general harmonics they produce. the harmonics produced by electric locomotive have a characteristic that their range and phase are both dispersive. this paper also analyzes the impedance - matching balance transformer ' s structure and harmonics injected into the power system at its primary side, and sums up the characteristics of the harmonics from electric traction loads in the tangyin traction substation

    鑒于湯陰變站的主要來自力牽引負荷,本文列舉了力機車幾種主要車型的結構以及它們產生的概況,得出了力機車的各次諧波電流幅值和相角具有較大分散性的特點。針對湯陰牽引變站的牽引變壓器,分析了阻抗匹配平衡變壓器的結構及其高壓側注入網的,推導了有關計算公式。通過理論分析並結合湯牽線的實測數據,歸納了力牽引負荷注入湯陰變站的的特點。